Appendix b: ms-9200, Capabilities, Testing – Fire-Lite ACM-8RF Control Relay Module User Manual

Page 31: Wiring, Ms-9200 terminal blocks, Nonresettable 24 vdc power out tb4(+) & (–)

Advertising
background image

ACM-8RF PN 50362:C 03/21/01

31

Appendix B: MS-9200

Capabilities

When installed with an MS-9200 Fire Alarm Control Panel (FACP), the ACM-
8RF Relay Control Modules provide relay activation (alarm only or alarm/
trouble) for each of the 56 FACP zones. Output activation for System Alarm,
System Trouble, Alarm Silence, Walktest, Supervisory, NAC Fault, Battery
Trouble and AC Fail are also available. Up to 32 ACM-8RF Relay Control
Modules may be placed onto the EIA-485 communication bus (if no other
devices are installed on the bus).

Testing

It is vitally important that, following relay programming, all relays be tested
for correct activation by triggering zones and/or special functions at the FACP.
It should also be noted:

ACM-8RF relays will activate during the Alarm Pre-signal Sequence.

• ACM-8RF relays will not activate during the Alarm Verification

Retard and Reset periods.

Wiring

Wire the AMC-8RF to the MS-9200 control panel as shown below.

Figure 16 Wiring ACM-8RF to MS-9200

24 V UN R EG 24 V NON R S 24 V RST

BE LL 2 PO WER

BE LL 1 PO WER

SU P V

AL AR M

TR OUB LE

PC /PR INTER
TER M C O MM

+ - + - + -

B+ A + A- B-

B+ A + A- B-

NO C NO NC C NO NC C

A B B+ A+ B- A -

1 C O MM 2

AC S

SH IEL D

SL C

SL C

O U T+ IN+ O UT- IN -

T
B
4

T
B
2

T
B
1

T
B
3

T
B
7

T
B
5

T
B
6

1 2

O

F

F

1

2

3

4

5

6

7

8

O
F

F

ACM-8RF

EIA-485
TB5 (+) & (–)

Nonresettable
24 VDC
Power Out
TB4(+) & (–)

MS-9200 Terminal Blocks

A

C

M8R

F

-ms9

200.cd

r

120 ohm ELR
Part #71244

Advertising