Alarm and trouble activation, Configuration appendix c: ms-9600, Table 17 sw3 settings for alarm/trouble - zones – Fire-Lite ACM-8RF Control Relay Module User Manual

Page 41

Advertising
background image

Configuration

Appendix C: MS-9600

ACM-8RF PN 50362:C 03/21/01

41

Alarm and Trouble Activation

When “Alarm/Trouble” is selected, relays 1 - 4 respond to alarm signals and
relays 5 - 8 respond to trouble signals.

The following table displays an example of how to set the DIP switches on four
(4) ACM-8RFs to annunciate the zones of an annunciator address. Although
this table shows System Points & Zones 1 to 8 (address 01), by referring to Table
13 on page 38 i
t can be determined which ACM-8RF will activate what zone
or point, depending on the address that is set on the rotary switches.

Table 17 SW3 Settings for Alarm/Trouble - Zones

Note: If the System Points (system alarm, trouble or silence etc.) is not required, up to
fourteen (14) ACM-8RFs may be used to allow activation of FACP zones 1 through 56.
When using this configuration do not use the DIP Switch settings for the 1st ACM-8RF.

ACM-8RF

Alarm Relay

MS-9600 Zone

ACM-8RF

Trouble Relay

MS-9600 Zone

1st ACM-8RF
SW3-1 = ON
SW3-5 = ON
All others = OFF

1=System Alarm

System Point

5=System Trouble

System Point

2 (not used)

System Point

Relay 6 (not used)

System Point

3 (not used)

System Point

7=System Off Normal

System Point

4 (not used)

System Point

8=System Supervisory

System Point

2nd ACM-8RF
SW3-2 = ON
SW3-5 = ON
All others = OFF

1 (not used)

System Point

5=NAC Fault

System Point

2 (not used)

System Point

6=Walktest Start

System Point

3 (not used)

System Point

7=Battery Fail

System Point

4 (not used)

System Point

8=AC Fail

System Point

3rd ACM-8RF
SW3-3 = ON
SW3-5 = ON
All others = OFF

Relay 1

Zone 1

Relay 5

Zone 1

Relay 2

Zone 2

Relay 6

Zone 2

Relay 3

Zone 3

Relay 7

Zone 3

Relay 4

Zone 4

Relay 8

Zone 4

4th ACM-8RF
SW3-4 = ON
SW3-5 = ON
All others = OFF

Relay 1

Zone 5

Relay 5

Zone 5

Relay 2

Zone 6

Relay 6

Zone 6

Relay 3

Zone 7

Relay 7

Zone 7

Relay 4

Zone 8

Relay 8

Zone 8