Setting the dip switches, Alarm only activation – Fire-Lite ACM-8RF Control Relay Module User Manual

Page 40

Advertising
background image

Appendix C: MS-9600

Configuration

40

ACM-8RF PN 50362:C 03/21/01

Setting the DIP Switches

The DIP switch (SW3), in combination with the Rotary Switches, is used to
determine which FACP activations will trigger relays on the ACM-8RF.

As described previously, the selection of “Alarm Only” or “Alarm/Trouble”
will determine how each module controls its relays. The difference between
these two settings is described below.

Alarm Only Activation

When “Alarm Only” is selected all relays respond to alarm signals.

The following table displays a dual example (zones & modules) of how to set
the DIP switches on two (2) ACM-8RFs to annunciate the zones or points of
an annunciator address. Although this table shows System Points & Zones 1
to 8 (address 01) and Loop 1, Points M65 to M80 (address 05), by referring to
Table 13 on page 38 it can be determined which ACM-8RF will activate what
zone or point, depending on the address that is set on the rotary switches.

Table 16 SW3 Settings for Alarm Only

Note: If the System Points (system alarm) is not required, up to seven (7) ACM-8RFs
may be used to allow activation of FACP zones 1 through 56. When using this
configuration do not use the DIP Switch settings for the 1st ACM-8RF.

ACM-8RF

Relay

MS-9600 Zone

1

or Point

2

1. As per Table 13 the Rotary Switches (SW1 & SW2) are set to address ‘01’ for

System Points and Zones 1 to 56.

2. As per Table 13 the Rotary Switches (SW1 & SW2) are set to address ‘05’ for

Loop 1, Address M65 to M128.

1st ACM-8RF
SW3-1 = ON
SW3-5 = ON
All others = OFF

Relay 1

System Alarm

or

Loop 1, Address M65

Relay 2

Not Used

or

Loop 1, Address M66

Relay 3

Not Used

or

Loop 1, Address M67

Relay 4

Not Used

or

Loop 1, Address M68

Relay 5

Not Used

or

Loop 1, Address M69

Relay 6

Not Used

or

Loop 1, Address M70

Relay 7

Not Used

or

Loop 1, Address M71

Relay 8

Not Used

or

Loop 1, Address M72

2nd ACM-8RF
SW3-2 = ON
SW3-5 = ON
All others = OFF

Relay 1

Zone 1

or

Loop 1, Address M73

Relay 2

Zone 2

or

Loop 1, Address M74

Relay 3

Zone 3

or

Loop 1, Address M75

Relay 4

Zone 4

or

Loop 1, Address M76

Relay 5

Zone 5

or

Loop 1, Address M77

Relay 6

Zone 6

or

Loop 1, Address M78

Relay 7

Zone 7

or

Loop 1, Address M79

Relay 8

Zone 8

or

Loop 1, Address M80

Advertising