FACP Activations
Appendix B: MS-9200
ACM-8RF PN 50362:C 03/21/01
35
Status functions of first 16 relays if the FACP has a UDACT-F installed.
Table 12 Status Relays (with UDACT-F)
MS-9200 Zone
ACM-8RF
Alarm Relay
ACM-8RF Trouble
Relay
SW3 Settings
System Status
1 System Alarm
5= System Trouble
1st ACM-8RF
SW3-1 = ON
SW3-5 = ON
All others = OFF
System Status
Relay 2 (not used)
6=Alarm Silence
System Status
Relay 3 (not used)
7=Walk Test
System Status
Relay 4 (not used)
8=Supervisory
System Status
Relay 1 (not used)
5=NAC Fail
2nd ACM-8RF
SW3-2 = ON
SW3-5 = ON
All others = OFF
System Status
Relay 2 (not used)
Relay 6 (not used)
System Status
Relay 3 (not used)
7=Battery Trouble
System Status
Relay 4 (not used)
8=AC Fail