Fire-Lite ACM-8RF Control Relay Module User Manual

Page 29

Advertising
background image

Application Example #4

Appendix A: MS-5210UD

ACM-8RF PN 50362:C 03/21/01

29

Since each ACM-8RF module contains eight relays, two ACM-8RF modules
are required for 10 zones of Alarm Only Relays and three ACM-8RF modules
are required for 10 zones of Alarm and Trouble Relays (20 relays required).

Table 9 Settings for Zone Alarm and Trouble Activation with LED-10s

MS-5210UD

Zone

ACM-8RF

Alarm Relay

ACM-8RF

Trouble Relay

Switch Settings

Z1

Relay 1

1st ACM-8RF
SW1=0; SW2=3 (Address ‘03’)
SW3-2 = ON; SW3-5 = ON
All other SW3s = OFF
SW4-1=ON; SW4-2=ON

Z2

Relay 2

Z3

Relay 3

Z4

Relay 4

Z5

Relay 5

Z6

Relay 6

Z7

Relay 7

Z8

Relay 8

Z9

Relay 1

2nd ACM-8RF
SW1=0; SW2=3 (Address ‘03’)
SW3-3 = ON; SW3-5 = ON
All other SW3s = OFF
SW4-1=ON; SW4-2=OFF

Z10

Relay 2

n/a

Relay 3

n/a

Relay 4

n/a

Relay 5

n/a

Relay 6

n/a

Relay 7

n/a

Relay 8

Z1

Relay 1

Relay 5

3rd ACM-8RF
SW1=0; SW2=4 (Address ‘04’)
SW3-3 = ON; SW3-5 = ON
All other SW3s = OFF
SW4-1=OFF; SW4-2=ON

Z2

Relay 2

Relay 6

Z3

Relay 3

Relay 7

Z4

Relay 4

Relay 8

Z5

Relay 1

Relay 5

4th ACM-8RF
SW1=0; SW2=4 (Address ‘04’)
SW3-4 = ON; SW3-5 = ON
All other SW3s = OFF
SW4-1=OFF; SW4-2=ON

Z6

Relay 2

Relay 6

Z7

Relay 3

Relay 7

Z8

Relay 4

Relay 8

Z9

Relay 1

Relay 5

5th ACM-8RF
SW1=0; SW2=4 (Address ‘04’)
SW3-1 = ON; SW3-6 = ON
All other SW3s = OFF
SW4-1=OFF; SW4-2=OFF

Z10

Relay 2

Relay 6

n/a

Relay 3

Relay 7

n/a

Relay 4

Relay 8