Appendix A: MS-5210UD

FACP Activations

22

ACM-8RF PN 50362:C 03/21/01

FACP Activations

DIP switch SW3 on the ACM-8RF Relay Control Module is used to determine
which FACP activations will trigger relays on the Relay Control Module.
When installed with an MS-5210UD Fire Alarm Control Panel, use the
following tables to set SW3 switches. Note that two tables are provided; one
table for alarm only operation (SW4-1 = ON) and one table for alarm and
trouble operation (SW4-1 = OFF).

Alarm Only Activation

Table 4 provides the switch settings for ACM-8RF DIP switch SW3 when
configuring the relays to trigger for alarm activation only. Note that a
maximum of three ACM-8RFs are required if one relay is to be designated to
trigger on any FACP alarm. If a general system alarm relay is not required, two
ACM-8RFs may be used to allow individual relay triggering for activation of
FACP zones 1 through 10. When using only two ACM-8RFs, be sure to use
the switch settings for the 2nd and 3rd ACM-8RF in Table 4. Refer to "Relay
Assignment DIP Switch - SW3" on page 15
for information on setting DIP
switch SW3.

Table 4 SW3 Settings for Alarm Only

MS-5210UD Zone

ACM-8RF Relay

SW3 Settings

System Alarm

Relay 1

1st ACM-8RF
SW3-1 = ON
SW3-5 = ON
All others = OFF

Not Used

Relay 2 (not used)

Not Used

Relay 3 (not used)

Not Used

Relay 4 (not used)

Not Used

Relay 5 (not used)

Not Used

Relay 6 (not used)

Not Used

Relay 7 (not used)

Not Used

Relay 8 (not used)

Z1

Relay 1

2nd ACM-8RF
SW3-2 = ON
SW3-5 = ON
All others = OFF

Z2

Relay 2

Z3

Relay 3

Z4

Relay 4

Z5

Relay 5

Z6

Relay 6

Z7

Relay 7

Z8

Relay 8

Z9

Relay 1

3rd ACM-8RF
SW3-3 = ON
SW3-5 = ON
All others = OFF

Z10

Relay 2

n/a

Relay 3 (not used)

n/a

Relay 4 (not used)

n/a

Relay 5 (not used)

n/a

Relay 6 (not used)

n/a

Relay 7 (not used)

n/a

Relay 8 (not used)