Mode Select

Alarm Only or Alarm/Trouble Mode

Determine if “alarm only” mode or “alarm/trouble” mode is to be used and set
the Mode Select switch SW4-1 as described in "Mode Select Switch - SW4"
on page 16 a
nd below.

If “alarm only” is selected, relays 1 to 8 will activate when an alarm signal is
received from a zone or point.

Table 14 Alarm Only Setup

If “alarm/trouble” is selected, then relays 1 to 4 will activate when an alarm
signal is received from a zone or point and relays 5 to 8 will activate when a
trouble signal is received from a zone or point.

Table 15 Alarm and Trouble Setup

Receive Only or Receive/Transmit Mode

Determine if “receive only” mode or “receive/transmit” mode is to be used and
set the Mode Select switch SW4-2 as described in "Mode Select Switch - SW4"
on page 16.

Note: Only one EIA-485 device per address may be set for receive/transmit.

Zone or Point

Alarm

Signal

1, 9, 17 etc. or 65, 73, 81 etc.

Relay 1

2, 10, 18 etc. or 66, 74, 82 etc.

Relay 2

3, 11, 19 etc. or 67, 75, 83 etc.

Relay 3

4, 12, 20 etc. or 68, 76, 84 etc.

Relay 4

5, 13, 21 etc. or 69, 77, 85 etc.

Relay 5

6, 14, 22 etc. or 70, 78, 86 etc.

Relay 6

7, 15, 23 etc. or 71, 79, 87 etc.

Relay 7

8, 16, 24 etc. or 72, 80, 88 etc.

Relay 8

Zone or Point

Alarm

Signal

Zone or Point

Trouble

Signal

1, 9, 17 etc. or 65, 73, 81 etc.

Relay 1

5, 13, 21 etc. or 69, 77, 85 etc.

Relay 5

2, 10, 18 etc. or 66, 74, 82 etc.

Relay 2

6, 14, 22 etc. or 70, 78, 86 etc.

Relay 6

3, 11, 19 etc. or 67, 75, 83 etc.

Relay 3

7, 15, 23 etc. or 71, 79, 87 etc.

Relay 7

4, 12, 20 etc. or 68, 76, 84 etc.

Relay 4

8, 16, 24 etc. or 72, 80, 88 etc.

Relay 8