FACP Activations

Appendix B: MS-9200

ACM-8RF PN 50362:C 03/21/01

33

Alarm and Trouble Activation

Table 11 provides the switch settings for ACM-8RF DIP switch SW3 when
configuring the relays to trigger for MS-9200 alarm and trouble activation. A
maximum of 16 ACM-8RFs are required if relays are to be designated to trigger
on any FACP status change. If system status relays are not required, 14 ACM-
8RFs may be used to allow individual relay triggering for alarm and trouble
activation of FACP zones 1 through 56. When using 14 ACM-8RFs, be sure
to use the switch settings for the 3rd through the 16th ACM-8RF in Table 11.

When the MS-9200 is programmed for an annunciator without a UDACT-F,
the first 16 relays will be assigned to the status functions listed in the table
below.
If the MS-9200 is programmed for an annunciator and a UDACT-F, the first
16 relays will be assigned to the status functions listed in Table 12 on page 35.

MS-9200

Zone

ACM-8RF

Alarm

ACM-8RF

Trouble

Switch Settings

System Status

1=System Alarm

5=System Trouble

1st ACM-8RF
SW3-1 = ON;
SW3-5 = ON
All other SW3s = OFF

System Status

Relay 2 (not used)

6=Alarm Silence

System Status

Relay 3 (not used)

Relay 7 (not used)

System Status

Relay 4 (not used)

Relay 8 (not used)

System Status

Relay 1 (not used)

5= Supervisory

2nd ACM-8RF
SW3-2 = ON;
SW3-5 = ON
All other SW3s = OFF

System Status

Relay 2 (not used)

Relay 6 (not used)

System Status

Relay 3 (not used)

Relay 7 (not used)

System Status

Relay 4 (not used)

8= Panel Trouble

Z1

Relay 1

Relay 5

3rd ACM-8RF
SW3-3 = ON;
SW3-5 = ON
All other SW3s = OFF

Z2

Relay 2

Relay 6

Z3

Relay 3

Relay 7

Z4

Relay 4

Relay 8

Z5

Relay 1

Relay 5

4th ACM-8RF
SW3-4 = ON;
SW3-5 = ON
All other SW3s = OFF

Z6

Relay 2

Relay 6

Z7

Relay 3

Relay 7

Z8

Relay 4

Relay 8

Z9

Relay 1

Relay 5

5th ACM-8RF
SW3-1 = ON;
SW3-6 = ON
All other SW3s = OFF

Z10

Relay 2

Relay 6

Z11

Relay 3

Relay 7

Z12

Relay 4

Relay 8

Z13

Relay 1

Relay 5

6th ACM-8RF
SW3-2 = ON;
SW3-6 = ON
All other SW3s = OFF

Z14

Relay 2

Relay 6

Z15

Relay 3

Relay 7

Z16

Relay 4

Relay 8

Z17

Relay 1

Relay 5

7th ACM-8RF
SW3-3 = ON;
SW3-6 = ON
All other SW3s = OFF

Z18

Relay 2

Relay 6

Z19

Relay 3

Relay 7

Z20

Relay 4

Relay 8

Table 11 SW3 Settings for Alarm and Trouble