Appendix C: MS-9600

Capabilities

When installed with an MS-9600 Fire Alarm Control Panel (FACP), the ACM-
8RF Relay Control Modules provide relay activation (alarm only or alarm/
trouble) for: each of the 99 FACP zones; the two NACs; each of the 159
modules and 159 detectors on both SLC loops. Output activation for System
Alarm, System Trouble, Alarm Silence, Walktest, Supervisory, NAC Fault,
Battery Trouble and AC Fail are also available. Up to 32 ACM-8RF Relay
Control Modules may be placed onto the EIA-485 communication bus (if no
other devices are installed on the bus).

Testing

It is vitally important that, following relay programming, all relays be tested
for correct activations by triggering zones, points and special functions at the
FACP. It should also be noted:

ACM-8RF relays will activate during the Alarm Pre-signal Sequence.

• ACM-8RF relays will not activate during the Alarm Verification

Retard and Reset periods

Wiring

Wire the ACM-8RF to the MS-9600 control panel as shown below.

Figure 17 Wiring ACM-8RF to MS-9600

TB 3

TB 4

TB 5

TB 6

TB 7

TB 8

1

2

O

F

F

1

2

3

4

5

6

7

8

O
F

F

ACM-8RF

EIA-485
TB6 (+) & (–)

Nonresettable
24 VDC
Power Out
TB3(+) & (–)

MS-9600 Terminal Blocks

A

C

M

8

R

F

-m

s960

0.cdr

120 ohm ELR
Part #17244