Alarm and trouble activation, Facp activations appendix a: ms-5210ud – Fire-Lite ACM-8RF Control Relay Module User Manual

Page 23

Advertising
background image

FACP Activations

Appendix A: MS-5210UD

ACM-8RF PN 50362:C 03/21/01

23

Alarm and Trouble Activation

Table 5 provides the switch settings for ACM-8RF DIP switch SW3 when
configuring the relays to trigger for alarm and trouble activation. Note that a
maximum of five ACM-8RFs are required if relays are to be designated to
trigger on any FACP status change. If system status relays are not required,
three ACM-8RFs may be used to allow individual relay triggering for alarm
and trouble activation of FACP zones 1 through 10. When using only three
ACM-8RFs, be sure to use the switch settings for the 3rd, 4th and 5th
ACM-8RF in Table 5.

Table 5 SW3 Settings for Alarm and Trouble

MS-5210UD

Zone

ACM-8RF

Alarm Relay

ACM-8RF Trouble

Relay

SW3 Settings

System Status

1=System Alarm

5=System Trouble

1st ACM-8RF
SW3-1 = ON
SW3-5 = ON
All others = OFF

System Status

Relay 2 (not used)

Relay 6 (not used)

System Status

Relay 3 (not used)

7=System Off Normal

System Status

Relay 4 (not used)

8=System Supervisory

System Status

Relay 1 (not used)

5=NAC(s) Fault

2nd ACM-8RF
SW3-2 = ON
SW3-5 = ON
All others = OFF

System Status

Relay 2 (not used)

6=Walktest Start

System Status

Relay 3 (not used)

7=Battery Fail

System Status

Relay 4 (not used)

8=AC Fail

Z1

Relay 1

Relay 5

3rd ACM-8RF
SW3-3 = ON
SW3-5 = ON
All others = OFF

Z2

Relay 2

Relay 6

Z3

Relay 3

Relay 7

Z4

Relay 4

Relay 8

Z5

Relay 1

Relay 5

4th ACM-8RF
SW3-4 = ON
SW3-5 = ON
All others = OFF

Z6

Relay 2

Relay 6

Z7

Relay 3

Relay 7

Z8

Relay 4

Relay 8

Z9

Relay 1

Relay 5

5th ACM-8RF
SW3-1 = ON
SW3-6 = ON
All others = OFF

Z10

Relay 2

Relay 6

n/a

Relay 3 (not used)

Relay 7 (not used)

n/a

Relay 4 (not used)

Relay 8 (not used)