Relay, Zones (see, Zones – Fire-Lite PS Tools MS-9600 User Manual

Page 36: Special zones

Advertising
background image

28

636 Pt Addr.Panel

PS-Tools

04/2010

Configuring Fire Panels

Relay

The fire panel consists of one fixed and two programmable Form-C dry contact relays. The fixed
fail-safe relay monitors system troubles. The two programmable relays are factory default. They can
be programmed for system alarm and system supervisory, and configured for the following
operations.

Fire alarm

Trouble

Supervisory

Supervisory auto-resettable

DACT communication failure

Process monitor

Process monitor auto-resettable

Hazard alert

Medical alert

AC loss.

To configure the relays

1.

Under Relays, select the type for Relay 1 from the drop-down list.

By default, Relay 2 is disabled and set to Trouble.

2.

Select the type for Relay 3. (see

Figure 5-3

)

Zones

In the input/output zones configuration, you can specify the zone type only if a DACT programmed
for zone reporting, is installed on the fire alarm control panel.

To configure each zone

1.

Under Zones, select the Zone Type from the list. Selecting WATERFLOW option assigns a
Waterflow silenceable zone type to the selected zone. Any signaling devices programmed to
the same zone can be silenced by pressing the Alarm Silence key or by using the Auto-silence
feature.

2.

Under Enabled/Disabled, select Enable to enable the zone. If you select Disable, the zone is
disabled by the fire panel, preventing the zone circuit from reporting alarms and troubles to the
panel. Disabling a zone disables all the functionalities associated with that zone.

Note

Programming the Zone Message is not supported in this release.

Special Zones

The zones 97, 98, and 99 can be programmed for normal zone operation or for special purpose
applications. If the zones are not selected, they are assigned to input and output devices.