Configuring Optional Modules

The optional modules installed in the 636 Pt Addr. system include ACM Series annunciators, graphic
and LCD annunciators.

Figure 5-6

Configuring Optional Modules

To configure the optional modules

1.

Click EIA-485 Terminal Mode Enabled, to enable the LCD-80F terminal mode annunciator.
This feature allows a series of up to 32 LCD-80F annunciators to be connected to the FACP’s
EIA-485 Terminal Mode connector.

2.

Click UDACT-F Communicator Installed, to allow a UDACT-F communicator to connect to
the FACP using the RS-485 ACS connector. If this feature is enabled, the reporting style for the
UDACT-F can be selected between point and zone.

3.

Click Annunciators, to allow a series of ACS annunciators, to be connected to the RS-485
ACS connector on the fire panel. If this feature is enabled, each ACS address can be
individually enabled/disabled.

4.

Click Save to Database to save the configuration in the PS-Tools database.

5.

Click Next in ANN-BUS or click Detectors in SLC Loop Setup in the left pane, to view the
SLC Loop Setup -> Detectors configuration pane.

6.

Click Prev to view the General System Settings pane for the 636 Pt Addr. system.