Trouble reminder, Water flow devices silenceable, Canadian option enabled – Fire-Lite PS Tools MS-9600 User Manual

Page 41

Advertising
background image

PS-Tools User Guide

636 Pt Addr. Panel

PS-Tools

04/2010

33

2.

Type the Maintenance password to change the factory set password for maintenance level
programming in the fire panel.

Note

Both Master and Maintenance passwords must consist of exactly 5 numbers.

Trouble Reminder

Click Trouble Reminder to enable the trouble reminder option. By default, this option is disabled.

Water Flow Devices Silenceable

Click Water Flow Devices Silenceable to enable the Water Flow Devices Silenceable option. By
default, this option is disabled.

Canadian Option Enabled

To configure Canadian Option

1.

Click Canadian Option Enabled.

a.

Ensure the input/output zone types are defined as in

Table 5-1

b.

You can set the Auto Silence option for NACs, only to No AutoSilence or 20 minutes.
NACs, which are programmed as No AutoSilence, remain in the same mode when
Canadian Option is enabled.

If NAC is programmed for Auto Silence, the default time is 20 minutes. If you set the auto
silence time to a value such as 10 or 30 minutes, it is automatically reset to 20 minutes.

Table 5-1

Zone and Module types available for Canadian option

Module types blocked from selection

Changes to

Monitor

Pull Station

MON User defined 3

Pull Station

MON User defined 7, 8, 9, 13, 16, and 17

Supervisory

Medical, Hazard, and Tornado Alert

Supervisory

Supervisory AR (Non-Latching)

Supervisory

Process Monitor AR and Process Monitor

Supervisory

Drill Switch AR (Non-Latching)

Drill Switch