Timers, Clock format, Fire panel passwords – Fire-Lite PS Tools MS-9600 User Manual

Page 40

Advertising
background image

32

636 Pt Addr.Panel

PS-Tools

04/2010

Configuring Fire Panels

Timers

You can program the fire panel for PAS or Presignal operation, not both. If you set the PAS Delay
timer with a value greater than 000, and then set the Presignal Delay timer with a value greater than
000, the PAS Delay timer is automatically reset to 000. Only one of the two timers can have a delay
time set.

To configure the timers

1.

Select a Positive Alarm Sequence Delay of 001 to 180 seconds for all devices programmed for
PAS. The factory default setting is 000 for no delay.

2.

Select a Alarm Presignal Delay of 001 to 180 seconds for all devices programmed for
Presignal. The factory default setting is 000 for no delay.

3.

Select a Waterflow Retard of 01 to 90 seconds for all devices programmed for Waterflow
delay. The factory default setting for Waterflow delay is 000 for no delay. A delay can be added
prior to declaring a waterflow type of alarm.

Note

Ensure to include the built-in delays of the waterflow device.

4.

You can delay the reporting of an AC power loss to a central station by setting the length of the
desired delay. Type the AC Loss Delay in hours (00 to 23 hour delay). The factory default
setting is 02 hours (see

Figure 5-5

).

Note

For Central Station applications, AC Loss Delay must be set to a delay value ranging
from 06 to 12 hours. For Remote Station applications, AC Loss Delay must be set to a
delay value ranging from 15 to 23 hours.

Clock Format

To configure the Clock Format

1.

Select the clock format as 24 hours or 12 hours.

a.

If you set the 24 Hour Format, the Time is in military format (00:00:00 to 23:59:59) and
the Date is in DD/MM/YYYY format.

b.

If you set the 12 Hour Format, the Time is in 12 hours format (AM/PM) and the Date is in
MM/DD/YYYY format (see

Figure 5-5

).

Fire Panel Passwords

To configure the Fire Panel Password

1.

Type the Master password to change the factory set password for master level programming in
the fire panel.