Ann s/pg options, Ann-80 options – Fire-Lite PS Tools MS-9600 User Manual

Page 45

Advertising
background image

PS-Tools User Guide

636 Pt Addr. Panel

PS-Tools

04/2010

37

The ANN S/PG and ANN 80 settings are applicable globally for any ANN BUS address of the same
type. The ANN -IO and ANN LED settings are specific to an ANN BUS address.

ANN S/PG Options

The ANN-S/PG options allows you to the connect a remote serial or parallel printer to the FACP. This
helps you to log system events, detector status reports and event history. If Parallel port is selected,
you can supervise and set the offline timer for the printer. If Serial port is selected, you can set the
Baud Rate, Parity, Data Bits, and Stop Bits.

To configure ANN S/PG Options

1.

Under ANN S/PG options, select the type of Port for the printer connection.

a.

If you select Parallel port, then perform the following:

In the Printer Supervision list, select True to enable printer supervision.

In the Offline Timer box, enter offline for delay between 0 and 255.

b.

If you select Serial port, perform the following:

In Baud Rate list, select a baud rate in the range 2400, 9600, or 19200.

In Parity list, select Even, Odd, or None.

In Data Bits list, select 7 or 8 bits.

In Stop Bits list, select 0.5, 1, or 2.

ANN-80 Options

The ANN-80 Annunciator is a compact, 80 character, backlit LCD remote fire annunciator. It mimics
the display on the control panel and will annunciate device type, point alarm, trouble or supervisory
condition, zone assignment plus any custom alpha labels programmed into the FACP.
Communication between the ANN-80 and FACP is accomplished over a two wire RS-485 serial
interface employing the ANN-BUS communication format.

To configure the ANN-80 module

1.

Select Yes to enable the Lock Enable option which allows you to unlock the ANN-80 keypad
with its own key. If you select No, the keylock is ignored and the ANN-80 keypad buttons are
always enabled.

2.

Select Yes in Piezo Enable to enable the sounding of the piezo sounder on any installed
ANN-80 module. The piezo sounder is disabled when you select No.

3.

Select Yes in ACK Enable to enable the normal function of the ACK/Step Button on any
installed ANN-80 annunciator. This option is ignored if you select No.

4.

Select Yes in Silence Enable to enable the Silence Button on any installed ANN-80
annunciator.

5.

Select Yes in Reset Enable to enable the Reset Button on any installed ANN-80 annunciator.

6.

Select Yes in Drill Enable to enable the Drill Button on any installed ANN-80 annunciator (see