Fire-Lite PS Tools MS-9600 User Manual

Page 50

Advertising
background image

42

636 Pt Addr.Panel

PS-Tools

04/2010

Configuring Fire Panels

To add an addressable device to the SLC Loop

1.

In SLC Loop Setup -> Detectors pane, click Add Devices. The Add dialog box appears where
you can add detector devices to the SLC Loop.

2.

In Device Address, click Loop 1 or Loop 2, and specify the device Address which is a three
digit value between 001 to 159.

3.

To add only one device, click Single Device.

4.

To add more than one device, click Multiple Devices.

5.

Specify the number of devices you want to add in No. of devices.

6.

Select the Device Type from the list.

7.

To add a user defined device type, select USER-DEF-1 from the list, and click Edit Custom
Type
. Type the new type label in the displayed window and click OK.

8.

In Device Label, select the Adjective and the Noun which specify the device location. The
adjective and noun are specific descriptors to identify the device location. To add a custom
adjective/noun, select the Add New option from the adjective/noun list and specify the custom
adjective/noun in the displayed window. Custom Label displays the selected Adjective and
Noun.

9.

In Device Options, the Device Enabled option is selected by default (when you click Add
Device). If this option is not selected, the detector is not polled by the control panel, which
prevents the detector from reporting alarms and troubles to the panel. The control panel
displays the device type and address of the disabled device and activates the Trouble and
Disable LEDs.

10. To enable the Pre-Signal option for the device, click Pre-Signal Enabled. This option

programs the detector to delay panel activation for a preprogrammed time delay of up to three
minutes, while allowing for visual verification. The alarm relay and communicator respond to
the initial alarm immediately. In addition, Zone 98 activates immediately and can be
programmed to a control module, to activate a sounder or indicator designated for Presignal
indication (do not use a Notification Appliance Circuit for this purpose).

Advertising