Configuring Fire Panels

3.

Click NAC 1 - Silenceable to indicate if the notification appliance can be silenced by pressing
the Alarm Silence key. If the Silenceable option is not enabled, the selected NACs cannot be
silenced by pressing the Alarm Silence key or by the Auto Silence feature.

4.

Select the delay for NAC 1 Auto Silence from the list, to automatically silence the main circuit
board silenceable NACs after a programmed length of time. This option is disabled if the
Silenceable option is not selected.

5.

Select the NAC 1 Coding option to specify the type of output the main circuit board
notification appliances generates, when activated. For more information about each coding
selection, see

Appendix

.

6.

Select the NAC 1 Type Code from the list.

7.

Select the NAC 1 Synchronization Type which can be System Sensor, Wheelock, or Gentex.
Synchronization is a panel feature that controls the activation of notification appliances in such
a way that devices turn on and off at exactly the same time. For more information about
synchronization, see

Synchronized NAC Operation

.

Note

NAC Synchronization Type can be selected only for Sync Strobe or Strobe Sil Sync
NAC Type Code.

8.

Under Zone Mapping, type the two digit number corresponding to the zone assigned to NAC
1. A maximum of five zones can be configured for each main circuit board NAC. The factory
default for an unprogrammed device is Z00 for general alarm zone.

9.

Click Save to Database to save the configuration in the PS-Tools database.

10. Click Next or click NAC 2 in the left pane to configure NAC 2.

11. Repeat steps 1 to 9 to configure NAC 2, NAC 3, and NAC 4.

12. Click Next or click General System Settings in the left pane, to view the General System

Settings configuration pane.

13. Click Prev to view the settings for NAC 3.