Editing devices – Fire-Lite PS Tools MS-9600 User Manual
Page 51
PS-Tools User Guide
636 Pt Addr. Panel
PS-Tools
04/2010
43
11. To enable the PAS option for the device, click PAS Enabled. The PAS option programs the
detector to delay panel activation (including alarm relay and communicator) for a period of
fifteen seconds plus a programmable time of up to three minutes. Zone 97, however, activates
immediately and can be used to connect a signaling device to indicate PAS activation (do not
use a Notification Applicance Circuit for this purpose).
Note
For a device, you can enable the PAS option or the Pre-Signal option. You cannot
enable both options together.
12. The Device Walktestable option is selected by default. The Walktest feature allows you to test
the system devices without manually resetting the control panel after each device activation.
13. To enable the Alarm Verification option for the device, click Alarm Verification Enabled.
Alarm verification is used to confirm that a smoke detector activation is a true alarm condition
and not a false alarm.
14. You can map each device to five Zones. Type the two digit number corresponding to the zone
assigned to the device for Zone 1 to Zone 5. The factory default for an unprogrammed device
is Z00 for a general alarm zone.
15. Type the Additional Information about the detector being programmed. This information is
displayed as part of the device label on the panel display.
16. Click OK. The device is added to the SLC loop setup.
Note
The Device Silenceable option is disabled for the detectors.
Editing Devices
Using the Edit Device(s) option, you can edit the device type, device options, and change the zone
mapping.
To edit the devices in the SLC loop
1.
Select the check box corresponding to the device you want to edit in the SLC Loop Setup ->
Detectors pane. You can select only one device at a time.