5/10 Zone Panel

PS-Tools 07/2010

Configuring 5/10 Zones Fire Panel

Figure 5-3

Configuring Central Station Reporting

3.

Set the Trouble Call Limit to limit the number of troubles sent to the central Station at a
particular instant. The Trouble Call Limit is a programmed value between 0 and 99, for each
unique trouble within a 24-hour period.

4.

Click Next to configure the primary central station. Click Previous to go back to the Option
Modules
pane.

Primary Central Station

The primary central station is the first available central station the option modules contacts to report
the fire alarm system status, alarm, and trouble events.

To configure the primary central station

1.

Type the Phone Number of the primary central station. You can enter a maximum of 20
characters with valid entries being 0 to 9 and A to E.

2.

Select the Communication Format of the reports sent to the primary control station. The
communication format is determined by the type of receiver at the primary central station, to
which the option module transmits reports.

3.

Type the Account Code for the panel. Each panel has a unique Account Code assigned by
the primary central station depending on the communication format being used.