Configuring 5/10 Zones Fire Panel

Timers

To configure the Timers

1.

Select a PAS Delay of 001 to 180 seconds for all devices programmed for PAS. The factory
default setting is 120 seconds for PAS delay and 000 for no delay.

2.

Select a Pre Signal Delay of 001 to 180 seconds for all devices programmed for Pre Signal.
The factory default setting is 120 seconds for Pre Signal delay and 000 for no delay.

3.

Select a Waterflow Retard Delay of 01 to 90 seconds for all devices programmed for
Waterflow delay. The factory default setting for Waterflow delay is 000 for no delay. A delay
can be added prior to declaring a waterflow type of alarm.

Note

Ensure to include the built-in delays of the waterflow device.

4.

You can delay the reporting of an AC power loss to a central station by setting the length of
the desired delay. Type the AC Loss Delay in hours (00 to 23 hour delay). The factory
default setting is 02 hours (see

Figure 5-11

).

Day Light Savings

To configure the Day Light Savings feature

1.

Select Enable to enable the Day Light Savings feature.

2.

Select the Start Month and Start Week.

3.

Select the End Month and End Week (see

Figure 5-11

).

Others

To program the Other features

1.

Select Yes to enable the Trouble Reminder option. The default option is No.

2.

Select Yes to enable the Battery Charger Disabled option. The default option is No (see

Figure 5-11

).

3.

Select Yes to enable the Canadian Option option. The default option is No.