Appendix a, Zone types and action when activated, Appendix – Fire-Lite PS-Tools 5UD/10UD User Manual

Page 88: A 1 zone types and action when activated

Advertising
background image

5/10 Zone Panel
PS-Tools 07/2010

77

A

A

A

Appendix

This chapter lists the various zone types and action when activated, coding selections, and explains
the Two Stage Operation and Synchronized NAC operation.

Zone Types and Action When Activated

Zone Type

Action When Activated

Pull-Station

Fire Alarm

Waterflow

Fire Alarm Delayed (uses waterflow delay)

Waterflow Nonsilenceable

Fire Alarm (uses waterflow delay)

Combo

Fire/Supervisory (uses waterflow delay)

Combo AutoResettable
Supervisory

Fire/Supervisory AR, nonlatching (uses
waterflow delay)

2-Wire Detector

Fire Alarm

Normally Open Contact

Fire Alarm

Fire

Fire Alarm

Tamper

Supervisory

Supervisory

Supervisory, latching

Supervisory AutoResettable

Supervisory, nonlatching

Medic-Alert

Supervisory, latching

Hazard-Alert

Supervisory, latching

Tornado-Alert

Supervisory, latching

Proc-Mon

Piezo

Procmon-AutoResettable

Piezo, nonlatching

AC-Loss-Mon

Trouble