Download Configuration Data to Fire Panel

To download the configuration information to the fire panel

1.

Click Download to Panel to download the programming information for the input, output,
and option modules, zones, event codes, and the system setup information to the fire panel.

The PC Panel Communication Status displays the status that the configuration data is
saved in the database, after the download to fire panel is completed successfully.

2.

Click Date and Time to download the date and time settings to the fire panel.

3.

Click Manual Evacuate to generate a Drill Activated Trouble at fire panel. The Drill
Activated
trouble starts the sounding of all the Silenceable devices and NACs connected to
the FACP.

4.

Click Restore Evacuate to clear the Drill Activated Trouble and restore the fire panel to
Normal state. The sounding of the Silenceable devices and the NACs continues. You must
click Signal Silence in the fire panel keypad to stop the sounders and NACs.

5.

Click Trouble Silence to silence all the trouble events sounding in the fire alarm system.

6.

Click Enable/Disable Zone to download the zone settings to the fire panel.

7.

Click Clear History to clear all the History data in the fire panel. For more information about
History Data, see

History Data

.

8.

Click Clear Walktest Data to clear the walktest data in the fire panel. For more information
about Walktest Data, see

Walktest Data

.