To configure the ANN-RLY

1.

In ANN-RLY, select the input zone, alarm, supervisory, or trouble for each Relay (see

Figure 5-9

).

Figure 5-9

Configuring ANN-RLY and ANN-80 Options

ANN-80

The ANN-80 Annunciator is a compact, 80 character, backlit LCD remote fire annunciator which
mimics the FACP display. It also provides system status indicators for AC power loss, alarm,
trouble, supervisory, and alarm silenced conditions. The communication between the ANN-80 and
FACP is accomplished over a two wire serial interface employing the ANN-BUS communication
format. Two wires are required to connect the ANN-80 to the power supply.

To configure the ANN-80 module

1.

Select Yes to enable the Lock Enable option which allows you to unlock the ANN-80 keypad
with its own key. If you select No, the keylock is ignored and the ANN-80 keypad buttons are
always enabled.

2.

Select Yes in Piezo Enable to enable the sounding of the piezo sounder on any installed
ANN-80 module. The piezo sounder is disabled when you select No.

3.

Select Yes in ACK Enable to enable the normal function of the ACK/Step Button on any
installed ANN-80 annunciator. This option is ignored if you select No.

4.

Select Yes in Silence Enable to enable the Silence Button on any installed ANN-80
annunciator.

5.

Select Yes in Reset Enable to enable the Reset Button on any installed ANN-80 annunciator.

6.

Select Yes in Drill Enable to enable the Drill Button on any installed ANN-80 annunciator.