PS-Tools User Guide

5/10 Zone Panel

PS-Tools 07/2010

35

Figure 5-10

Configuring ANN-AUDIO 25/50 ZS

2.

Select between Zone 1 to Zone 10.

Configuring System Setup

System Setup allows you to configure the following fire panel features:

Time-Date (Clock Format and Day Light Savings) feature allows you to set the time, display
format (24 hour or 12 hour), date, and daylight savings time feature into the FACP memory.

Timers option allows you to set the PAS (Positive Alarm Sequence) time delay, Pre-Signal
time delay, Waterflow Retard delay, and AC Loss delay.

Banners option allows you to change the top two lines of the LCD display in the fire panel.
You can change the factory default readout to a custom defined readout, when the fire panel
is in Normal condition.

Trouble Reminder feature, when enabled, provides an audible reminder that an alarm or
trouble still exists on the FACP after the control panel has been silenced. If the Trouble
Reminder feature is disabled and a trouble condition is not cleared within 24 hours, the panel
sends an abnormal 24 hour test message to the central station if connected.

Charger Disable option allows you to disable the onboard battery charger if an external
battery charger is being used.

Canadian Option enables allows you to automatically monitor addressable ionization smoke
detector sensitivity using Canadian specifications. By default, this option is disabled.