Coding selection, Two stage operation, A 2 coding selection a 3 two stage operation – Fire-Lite PS-Tools 5UD/10UD User Manual

Page 89

Advertising
background image

78

5/10 Zone Panel

PS-Tools 07/2010

Appendix

Coding Selection

The Coding feature allows you to specify the type of output the main circuit board NAC generates,
when activated. The various coding selections are:

Steady - a continuous output with no coding

March Time - 120 ppm (pulse-per-minute) output

California - 10 seconds on and 5 seconds off

Temporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second on, 1½ second
off

Two Stage 3 Minutes or 5 Minutes - For more information about Two Stage Operation, see

Two Stage Operation

Synchronized output for System Sensor, Wheelock, Gentex, Faraday or Amseco. For more
information about Synchronized NAC Operation, see

Synchronized NAC Operation

.

Two Stage Operation

Two Stage operation consists of the following:

1st stage output - 20 ppm (pulse-per-minute) coding

2nd stage output - Temporal coding

If Two Stage operation is programmed as the Coding option, the following sequence of events
occurs during an alarm:

1.

The on-board NACs are activated with a 1st stage output on activation of any alarm point.

2.

If, after the programmed time of 3 or 5 minutes, the Acknowledge switch is not pressed, all
NACs presently in 1st stage activation go to the 2nd stage activation.

3.

If an Acknowledge switch is pressed, the NACs currently in 1st stage activation remain in 1st
stage. Pressing the Acknowledge switch does not affect NACs already in 2nd stage
activation.

Ack-Switch

Acts like panel Acknowledge Key

Sil-Switch

Acts like panel Alarm Silence Key

Drill-Switch

Acts like panel Drill Key

Reset-Switch

Acts like panel Reset Key

PAS-Bypass

Positive Alarm Sequence Disable

Drill-Switch AutoResettable

Acts like panel Drill Key, nonlatching

Zone Type

Action When Activated