L station (see, Secondary central station – Fire-Lite PS-Tools MS-9200UDLS User Manual

Page 35

Advertising
background image

PS-Tools User Guide

198 Pt Addr. Panel

PS-Tools

08/2010

27

4.

Select the desired Test Time Interval (6, 8, 12 or 24 hours) to send the test report to the
primary central station.

5.

Type the Test Start Time to program the time at which the optional modules run the test. Type
a four digit number using military time (0000 refers to 12:00AM and 2359 refers to 11:59PM).

6.

Click Save to Database to save the configuration.

7.

Click Next or click Secondary Central Station in the left pane, to configure the secondary
central station.

8.

Click Prev to view the central station settings.

Secondary Central Station

The secondary central station is the next available central station that the optional modules contact to
report the fire alarm system status, alarm, and trouble events. The configuration of the secondary
central station involves the same steps as the primary central station.

In addition you can specify if

the phone line requires supervision. For more information, see

Primary Central Station

.

After you configure the secondary central station:

Under Phone Line 2 Supervision, select Enabled for supervising the phone line 2.

Click Next to configure the input/output modules.

Alternatively, you can click Input/Output in the left pane to view the Input/Output
configuration pane.

Advertising