Fire-Lite PS-Tools MS-9200UDLS User Manual

Page 44

Advertising
background image

Configuring Fire Panels

36

198 Pt Addr. Panel

PS-Tools

08/2010

Figure 5-6

Configuring Optional Modules

To configure the optional modules

1.

Click EIA-485 Terminal Mode Enabled, to enable the LCD-80F terminal mode annunciator.
This feature allows a series of up to 32 LCD-80F annunciators to be connected to the FACP’s
EIA-485 Terminal Mode connector.

Note

If you enable EIA-485 Terminal Mode Enabled (LCD-80) option, then PC/Printer
Installed
option in System setup is disabled.

2.

Click UDACT-F Communicator Installed, to allow a UDACT-F communicator to connect to
the FACP using the RS-485 ACS connector. If this feature is enabled, the reporting style for the
UDACT-F can be selected between point and zone.

3.

Click Annunciators to allow a series of ACS annunciators, to be connected to the RS-485 ACS
connector on the fire panel. If this feature is enabled, each ACS address can be individually
enabled/disabled.

4.

Click Save to Database to save the configuration in the PS-Tools database.

5.

Click Next or click Detectors in SLC Loop Setup in the left pane, to view the SLC Loop
Setup -> Detectors
configuration pane.

6.

Click Prev to view the General System Settings pane for the 198 Pt Addr. panel.