Configuring Fire Panels

40

198 Pt Addr. Panel

PS-Tools

08/2010

ANN-80 Options

The ANN-80 Annunciator is a compact, 80 character, backlit LCD remote fire annunciator. It mimics
the display on the control panel and will annunciate device type, point alarm, trouble or supervisory
condition, zone assignment plus any custom alpha labels programmed into the FACP.
Communication between the ANN-80 and FACP is accomplished over a two wire RS-485 serial
interface employing the ANN-Bus communication format.

To configure the ANN-80 module

1.

Select Yes to enable the Lock Enable option which allows you to unlock the ANN-80 keypad
with its own key. If you select No, the keylock is ignored and the ANN-80 keypad buttons are
always enabled.

2.

Select Yes in Piezo Enable to enable the sounding of the piezo sounder on any installed
ANN-80 module. The piezo sounder is disabled when you select No.

3.

Select Yes in ACK Enable to enable the normal function of the ACK/Step Button on any
installed ANN-80 annunciator. This option is ignored if you select No.

4.

Select Yes in Silence Enable to enable the Silence Button on any installed ANN-80
annunciator.

5.

Select Yes in Reset Enable to enable the Reset Button on any installed ANN-80 annunciator.

6.

Select Yes in Drill Enable to enable the Drill Button on any installed ANN-80 annunciator(see

Figure 5-6

).

Note

You must enable the canadian option to configure the following ANN-80C modules.

To configure the ANN-80C module

1.

Select Yes in Piezo Enable to enable the sounding of the piezo sounder on any installed
ANN-80C module. The piezo sounder is disabled when you select No.

2.

Select Yes in Step Enable to enable the normal function of the ACK/Step Button on any
installed ANN-80C annunciator. This option is ignored if you select No.

3.

Select Yes in Silence Enable to enable the Silence Button on any installed ANN-80C
annunciator.

4.

Select Yes in LampTest Enable to enable the Reset Button on any installed ANN-80C
annunciator.

5.

Select Yes in Sounder Test Enable to enable the Drill Button on any installed ANN-80C
annunciator.

ANN LED Options

The ANN LED Option allows you to configure the optional ANN-LED annunciator.

To configure ANN LED Option

1.

Select Yes in Piezo Enable to enable the sounding of the piezo sounder on any installed
ANN-LED options module. The piezo sounder is disabled when you select No.

2.

Select Yes in the Lamp Test Enable to enable the lamp test button function normally on any
installed ANN-LED annunciator.