Configuring ANN Bus Settings
ANN-Bus is a communication terminal in the fire panel over which different ANN devices can be
installed to communicate with the FACP. The ANN devices such as ANN-S/PG Printer Interface
module, ANN-I/O LED Driver Module, ANN-LED Annunciator Module, ANN-RLY Relay module,
ANN-AUDIO, and other types can be installed in the fire alarm system. You can configure the
ANN-Bus, when any ANN devices are installed.
To configure the ANN Bus
1.
Click Next at the lower-right corner of the Optional Modules pane to view the ANN Bus
Settings pane or click ANN Bus Settings in the left pane.
2.
Click Yes in ANN Bus Enable to enable the ANN Bus. You must enable the ANN Bus, if ANN
devices are installed on the ANN Bus terminals.
Figure 5-7
Configuring Global Options
3.
Click Next to configure the Primary ANN Bus or click Primary ANN Bus in the left pane.
Figure 5-8
Configuring Primary ANN Bus
4.
In Primary ANN Bus Address, select the Module Type for each address. and then select the
Status.