Configuring Fire Panels

42

198 Pt Addr. Panel

PS-Tools

08/2010

ANN-AUDIO

The ANN-AUDIO 25/50 ZS All Call Zone series audio panel is used to play an audio message when
there is an alarm in one of the input zones. This audio panel connects to the FACP through the
ANN-Bus communication circuit.

You can select one of the five audio messages the audio panel plays, when an FACP input zone goes
into alarm. The message plays over the corresponding audio panel output circuit. The input zones can
be programmed as alarm type, supervisory type, process monitor type, or AC Loss Monitor.

Note

Ensure the input zone type is not Ack, Sil, Reset, or PAS Bypass switches.

Example: If FACP input zone 3 goes into alarm, the programmed message plays over the
ANN-AUDIO 25/50 ZS output circuit 3. If two or more input zones are active at the same time, the
highest priority message plays.

The connection between the fire panel and the ANN-AUDIO 25/50 ZS audio panel is accomplished
by a pair of communication wires connected between the A/B terminals on TB3 of the FACP and TB1
terminals 2 & 3 of the ACC-ZPMK module on the ANN-AUDIO 25/50 ZS.

ANN-Bus Address

ANN-Bus Address allows you to install the modules type in their respective 1-8 addresses.

To configure the ANN-Bus Address

1.

In Primary ANN Bus Address, select the Module Type for each address. and then select the
Status. (see

Figure 5-8

).

2.

In Secondary ANN Bus Address, select the Module Type for each address. and then select
the Status. (see

Figure 5-9

).

3.

Click Next to configure the Detectors or click Detectors Option in the left pane.