Ann bus, Ann s/pg options – Fire-Lite PS-Tools MS-9200UDLS User Manual

Page 47

Advertising
background image

PS-Tools User Guide

198 Pt Addr. Panel

PS-Tools

08/2010

39

ANN Bus

Click Yes to enable the ANN Bus. You must enable the ANN Bus if any modules are connected to
the ANN Bus terminal.

The following are the compatible devices that you can connect to the FACP ANN-Bus
communication circuit.

ANN-80 LCD Annunciator

ANN-S/PG Serial/Parallel Printer Interface Module

ANN-I/O LED Driver Module

ANN-LED Annunciator Module (alarm, trouble, supervisory LEDs)

ANN-RLED Annunciator Module (red alarm LEDs only)

ANN-RLY Relay Module to the ANN Bus

ANN-AUDIO

The ANN S/PG and ANN 80 settings are applicable globally for any ANN Bus address of the same
type. The ANN -IO and ANN LED settings are specific to an ANN Bus address.

ANN S/PG Options

The ANN-S/PG options allows you to the connect a remote serial or parallel printer to the FACP. This
helps you to log system events, detector status reports and event history. If Parallel port is selected,
you can supervise and set the offline timer for the printer. If Serial port is selected, you can set the
Baud Rate, Parity, Data Bits, and Stop Bits.

To configure ANN S/PG Options

1.

Under ANN S/PG options, select the type of Port for the printer connection.

a.

If you select Parallel port, then perform the following:

In the Printer Supervision list, select True to enable printer supervision.

In the Offline Timer box, type offline for delay between 0 and 255.

b.

If you select Serial port, perform the following:

In Baud Rate list, select a baud rate in the range 2400, 9600, or 19200.

In Parity list, select Even, Odd, or None.

In Data Bits list, select 7 or 8 bits.

In Stop Bits list, select 0.5, 1, or 2.

Advertising