Configuring Fire Panels

32

198 Pt Addr. Panel

PS-Tools

08/2010

Figure 5-5

Configuring System Setup Options

Timers

You can program the fire panel for PAS or Presignal operation, not both. If you set the PAS Delay
timer with a value greater than 000, and then set the Presignal Delay timer with a value greater than
000, the PAS Delay timer is automatically reset to 000. Only one of the two timers can have a delay
time set.

To configure the timers

1.

Select a Positive Alarm Sequence Delay of 001 to 180 seconds for all devices programmed for
PAS. The factory default setting is 000 for no delay.

2.

Select a Alarm Presignal Delay of 001 to 180 seconds for all devices programmed for
Presignal. The factory default setting is 000 for no delay.

3.

Select a Waterflow Retard of 01 to 90 seconds for all devices programmed for Waterflow
delay. The factory default setting for Waterflow delay is 000 for no delay. A delay can be added
prior to declaring a waterflow type of alarm.

Note

Ensure to include the built-in delays of the waterflow device.

4.

You can delay the reporting of an AC power loss to a central station by setting the length of the
desired delay. Type the AC Loss Delay in hours (00 to 23 hour delay). The factory default
setting is 02 hours (see

Figure 5-5

).