SLC Loop Setup

SLC loops provide communication to addressable detectors, monitor (initiating device), and control
(output device) modules. One SLC loop is provided by default on the fire panel main circuit board.
You can plug the optional SLC module into the connector, on the main circuit board for the second
SLC loop. The 198 Pt Addr. fire panel addressable device capacity is 99 detectors and 99
control/monitor modules per SLC loop.

You can configure the SLC Loop for NFPA Style 4, 6, or 7. The wiring styles Style 4 or Style 6 are
mostly used. Style 7 wiring is same as Style 6 with the added requirement that each addressable
device on the loop must have a pair of isolator modules, one on each side. To program a system for
Style 7, you must select the loop setup for Style 6. You can configure all the addressable devices to
SLC Loop 1, in the SLC Loop Setup screen.

Detectors

The SLC Loop Setup -> Detectors pane helps you to perform the following:

Add a new addressable detector to an SLC loop.

Delete an existing detector from a loop.

Change the programming for an existing detector.

Search for detector in a zone.

View the added detector in a tabular or graphical form.