PS-Tools User Guide

198 Pt Addr. Panel

PS-Tools

08/2010

53

10. To enable the Pre-Signal option for a module, click Pre-Signal Enabled option. The Pre-signal

option programs the module to delay panel activation for a preprogrammed time delay of up to
three minutes while allowing for visual verification.

Note

The PAS Enabled, Alarm Verification Enabled, and Device Silenceable options are
not enabled when you add modules to the SLC loop.

11. The Device Walktestable option is selected by default. The Walktest feature allows you to test

the system devices without manually resetting the control panel after each device activation.

12. You can map each module to five Zones. Type the two digit number corresponding to the zone

assigned to the device for Zone 1 to Zone 5. The factory default for an unprogrammed device
is Z00 for a general alarm zone.

13. Type Additional Information about the module being programmed. This information is

displayed as part of the device label on the fire panel display.

14. Click OK. The module is added to the SLC loop setup.