10. To enable the Pre-Signal option for a module, click Pre-Signal Enabled option. The Pre-signal
option programs the module to delay panel activation for a preprogrammed time delay of up to
three minutes while allowing for visual verification.
Note
The PAS Enabled, Alarm Verification Enabled, and Device Silenceable options are
not enabled when you add modules to the SLC loop.
11. The Device Walktestable option is selected by default. The Walktest feature allows you to test
the system devices without manually resetting the control panel after each device activation.
12. You can map each module to five Zones. Type the two digit number corresponding to the zone
assigned to the device for Zone 1 to Zone 5. The factory default for an unprogrammed device
is Z00 for a general alarm zone.
13. Type Additional Information about the module being programmed. This information is
displayed as part of the device label on the fire panel display.
14. Click OK. The module is added to the SLC loop setup.