HT instruments MACROTEST 5035 User Manual

Page 71

Advertising
background image

MACROTEST

5035

EN - 70

11.3. CHECK OF THE CIRCUIT SEPARATION
The test, to be effected in case the protection is realized through separation (SELV or
PELV or electrical separation), shall check that the insulation resistance measured
according to the indications below (depending on the separation type) complies with the
limits reported in the table relative to the insulation measurements.

INSTALLATIONPARTS TO BE CHECKED

SELV system (Safety Extra Low Voltage):

measure the resistance between the active parts of the circuit under test (separate)

and the active parts of the other circuits.

measure the resistance between the active parts of the circuit under test (separate)

and the earth.

The resistance shall not be lower than 0.25M

Ω with a test voltage of 250VDC.

PELV system (Protective Extra Low Voltage):

measure the resistance between the active parts of the circuit under test (separate)

and the active parts of the other circuits.

The resistance shall not be lower than 0.25M

Ω with a test voltage of 250VDC.

Electrical separation:

measure the resistance between the active parts of the circuit under test (separate)

and the active parts of the other circuits.

measure the resistance between the active parts of the circuit under test (separate)

and the earth.

The resistance shall not be lower than 0.5M

Ω with a test voltage of 500VDC and 1MΩ with

a test voltage of 1000VDC.

ALLOWABLE VALUES
The test result is positive when the insulation resistance indicates values higher or equal to
those indicated in the table reported in the section relative to insulation tests.

Please note that:
A

SELV system is a system of category zero or very low safety voltage featured by:

autonomous source (ex. batteries, small generator) or safety (ex. safety transformer)
power supply, protection separation to other electrical systems (double or reinforced
insulation or a metal screen connected to the earth) and no earthed points (insulated from
the earth).

A

PELV system is a system of category zero or very low safety voltage featured by:

autonomous source (ex. batteries, small generator) or safety (ex. safety transformer)
power supply, protection separation to other electrical systems (double or reinforced
insulation or a metal screen connected to the earth) and there are earthed points (not
insulated from the earth).

A system with

Electrical separation is featured by: insulation transformer or autonomous

source with equivalent features (ex. generator) power supply, protection separation to
other electrical systems (insulation not lower than that of the insulation transformer)and
protection separation to the earth (insulation not lower than that of the insulation.

Advertising