- 22 -

(2) Setting procedures

Follow the procedures below

[Stand-by state]
     

ENTER button(

)

Setting of Measurement duration (with UP/DOWN button (

))

     

ENTER button (

)

Setting of Output voltage*1 (with UP/DOWN button (

))

     

ENTER button (

)

Setting of Breakdown/Burn (with UP/DOWN button (

))

     

ENTER button (

)

Setting is finished.

(*1): 500V/2500V/5000V Range only

6-5-1 PI – Polarization index
This is to check a temporal increase of leakage currents flowing on insulations
and to confirm leakage currents aren’t increased as time passes.
PI is usually determined by the insulation resistances measured 1 min and 10
min after a measurement is started. PI is dependent on the shape of insulations
and influenced by moisture absorption, therefore, a check of PI is important to
diagnosis the insulation of cables.

PI =

Insulation resistance

(10 min after a start of test)

Insulation resistance

(1 min after a start of test)

PI

4 or more

4 - 2

2.0 - 1.0

1.0 or less

Criteria

Best

Good

Warning

Bad