Specification – KYORITSU 3127 User Manual

Page 9

Advertising
background image

- 6 -

3. Specification

Applicable standards

IEC 61010-1 Measurement CAT. IV 600V Pollution degree2

IEC 61010-031 Standard for hand-held probes

MODEL7165A(CAT. IV 600V)

MODEL7224A(CAT.IV 600V)

MODEL7225A(CAT.IV 600V)

* When KEW3127 and the test lead are combined and

used together, whichever is lower category either of

them belong to is applied.

IEC 61326-2-2 EMC standard

IEC 60529

IP40(Instrument)

IP65 (Hard case)

Measuring range and accuracy (Temperature, humidity: 23±5Cº, 45 - 75%RH)

<Insulation resistance tester>

Rated

voltage

250V(*1)

500V

1000V

2500V

5000V

Accuracy

Measuring

range(*2)

0.0-99.9MΩ 0.0-99.9M

Ω

100-999MΩ

0.0-99.9MΩ

100-999MΩ

1.00-1.99GΩ

0.0-99.9MΩ

100-999MΩ

1.00-9.99GΩ

10.0-99.9GΩ

0.0-99.9MΩ

100-999MΩ

1.00-9.99GΩ

10.0-99.9GΩ

±5%rdg

±3dgt

100-999MΩ

1.00-9.99GΩ

1.00-9.99GΩ

10.0-99.9GΩ

2.00-9.99GΩ

10.0-99.9GΩ

100-199GΩ

100-999GΩ 100-999G

Ω

1.00-9.99TΩ

±20%rdg

Display range 0.0M - 12.00GΩ 0.0M-120.0GΩ 0.0M-240GΩ 0.0M-1200GΩ 0.0M-12.00TΩ
Open circuit

voltage

DC 250V

+10%, -10%

DC 500V

+20%, -10%

DC 1000V

+20%, -0%

DC 2500V

+20%, -0%

DC 5000V

+20%, -0%

Rated

current

1mA or more,

1.2mA or less

(at 1MΩ load)

1mA or more,

1.2mA or less

(at 2.5MΩ load)

1mA or more,

1.2mA or less

(at 5MΩ load)

Short-circuit

current

For 10 sec after a test is started : max 5mA,

after that : 1.4mA

(*1) 250V Range is for IR

PI/DAR

measurement only.

(*2) Measuring range goes to one lower range when the applied input drops to

80% or lower of the rating of the lower range. Measurement accuracy to be

applied is changed when the range goes to the lower range.

Advertising