When DAR/PI values are displayed as“---”:

DAR and PI values are determined by the methods 1. and 2. as described
above, therefore, they are displayed as “---” when the measured insulation
resistances fall under any of following cases.

measured value is “0.0MΩ”

measured value is “OL”

*“ OL”is displayed when the measured value exceeds the upper limit of the

measuring range at each insulation resistance range.

Range

Upper limit

250V

12GΩ

500V

120GΩ

1000V

240GΩ

2500V

1200GΩ

5000V

12TΩ