Specification – KYORITSU 6201A User Manual

Page 11

Advertising
background image

— 9 —

4. Specification


4.1 General specification, measuring range and accuracy
Voltage(VOLT) measurement of main power supply

Measuring range

207 ~ 264V AC

Resolution

1V

Accuracy

± (2%rdg+3dgt)

Measurement of Protective conductor resistance(RPE)

Measuring range

0 ~ 15.00Ω

Resolution

10mΩ

Open-circuit voltage

<AC12V

Measuring current

10A AC nominal value

Accuracy

± (3%rdg+5dgt)

Measurement of Insulation resistance (RINS)

Rating

250V/20MΩ and 500V / 20MΩ

Measuring range

0.1~19.99MΩ

Resolution

10kΩ

Rated voltage

250V/500V DC(+20%/-10%) @1MΩ

Short-circuit current

2.5mA DC or less

Accuracy

± (2% rdg+3dgt)

Leakage current test

Measuring range

AC0.1~ 19.99mArms

Resolution

0.01mA

Accuracy

±(3%rdg ± 5dgt)

Examination time

Max 15 seconds

Note: For MOV appliances use Leakage Current test.

4.2 Threshold and display

Equipment

Protective conductor

resistance

Insulation

resistance

Leakage

current

Class I

RPE

=

<

RINS

>

=

1MΩ

IEL

=

<

5mA

Class II

RINS

>

=

1MΩ

IEL

=

<

1mA

Extension Leads

RPE

=

<

RINS

>

=

1MΩ

IEL

=

<

1mA

Advertising