KYORITSU 6201A User Manual

Page 24

Advertising
background image

— 22 —

• When the function is set to extension leads test while pressing Select

switch, Power on leakage current test will be carried out instead of

Insulation resistance test.

・ Protective conductor resistance between accessible conductive parts and

connection of protective earth.

 

・ Leakage Current test: Measure a leakage current by actually operating

the appliance.

Extension Leads Test (Select the Leakage current test) Flowchart

Start

#

CAUTION

• When the terminal is open or the resistance value exceeds measuring

range, OL mark (over range display) appears on the LCD.

• The test will stop. A message Stp appears on the LCD but values of

Leakage current aren't displayed.

(1). Protective conductor resistance test.

RPE <

= 1Ω?

(2). Power on Leakage current test

LEA <

= 1mA?

Light up in red

no” →“Con”→“value” will

be repeated on the LCD.

Light up in red

Stop the test and

no” →“LEA”→“value” will

be repeated on the LCD.

Value of (1). and (2). will be

alternately displayed on the LCD.

No

No

Yes

Yes

PASS

Light up in green

Light up in green

Brief indications“S-”and“on”will be displayed

in turns on the LCD for 5 sec and prompt the

user to set the DUT switch on.

Then a mark indicating working DUT function

will be displayed for 10 sec.

5sec

10sec