3.4 Error list / Maintenance manager

With one or several errors, the extended operating level al-

ways starts with the error list. Signalling an actual entry in

the error list (alarm, error) is done by the Err LED in the

display. To reach the error list press Ù twice.

Error list:

Operation

KS 90-1 / KS 92-1

13

Error list / Maintenance manager

1200

1199

°C

°F

SP.2

SP.E

para

func

Ada

Err

Err LED status

Signification

Proceed as follows

blinks

(status 2)

Alarm due to existing

error

- Determine the error type in the error list

- After error correction the unit changes to status 1

lit

(status 1)

Error removed, alarm

not acknowledged

- Acknowledgethealarmintheerrorlistpressingkey ÈorÌ

- The alarm entry was deleted (status 0).

off

(status 0)

No error, all alarm

entries deleted

- -Not visible except when acknowledging

Name

Description

Cause

Possible remedial action

E.1

Internal error,

cannot be removed

- E.g. defective EEPROM - Contact PMA service

- Return unit to our factory

E.2

Internal error, can be

reset

- e.g. EMC trouble

- Keep measurement and power supply

cables in separate runs

- Ensure that interference suppression

of contactors is provided

E.3

Configuration error,

can be reset

- wrong configuration

- missing configuration

- Check interaction of configuration /

parameters

E.4

Hardware error

- Codenumber and

hardware are not

identical

- Contact PMA service

- Elektronic-/Optioncard must be

exchanged

FbF.1

Sensor break INP1 - Sensor defective

- Faulty cabling

- Replace INP1 sensor

- Check INP1 connection

Sht.1

Short circuit INP1 - Sensor defective

- Faulty cabling

- Replace INP1 sensor

- Check INP1 connection

POL.1

INP1polarity error - Faulty cabling

- Reverse INP1 polarity

FbF.2

Sensor break INP2 - Sensor defective

- Faulty cabling

- Replace INP2 sensor

- Check INP2 connection

Sht.2

Short circuit INP2 - Sensor defective

- Faulty cabling

- Replace sensor INP2

- Check INP2 connection

POL.2

INP2 polarity

- Faulty cabling

- Reverse INP2 polarity

FbF.3

Sensor break INP3 - Sensor defective

- Faulty cabling

- Replace INP3 sensor

- Check INP3 connection

Sht.3

Short circuit INP3 - Sensor defective

- Faulty cabling

- Replace sensor INP3

- Check INP3 connection

POL.3

INP3 polarity

- Faulty cabling

- Reverse INP3 polarity