1 input inp.1 and inp.3 60, 2 input inp.2 60, 6calibration level – West Control Solutions Pro-4 User Manual

Page 60: Cal), Calibration level, Measured value correction

Advertising
background image

6

Calibration level

Measured value correction (

CAL)

is only visible if ConF / InP.1 / Corr = 1

or 2 is chosen.

The measured value can be matched in the calibration menu ( CAL). Two me-

thods are available:

Offset correction

( ConF/ InP.1 / Corr =1 ):

w possible on-line at the

process

2-point correction

( ConF/ InP.1 / Corr = 2 ):

w is possible off-line with

process value simulator

Calibration level

60

KS 90-1 / KS 92-1

X

standard setting

offset correction

InL.1

OuL.1

new

display

OuL.1

old

X

standard setting
2-point correction

InL.1

InH.1

OuL.1

new

OuH.1

new

display

OuH.1

old

OuL.1

old