7 special functions 64, 1 dac®œ motor actuator monitoring 64, Dac 64 - 65 – West Control Solutions Pro-4 User Manual

Page 64

Advertising
background image

Functioning of the DAC function

No input filter should be defined for the Yp input ( PArA / InP.x / t.Fx = 0 ).

Therewith no wrong detection of blocking or wrong method of operation can be

recognized.

The automatic calibration can be used with drives outfitted with spring assembly.
Execution of the calibration:

It is controlled if the mean alteration between two messurements is enough for

the DAC monitoring. The calibration will be stopped if the alteration between

two messurements is too small.

The position of 0% is searched. Therefor the drive will be closed until there is no

changing of the input signal for 0,5 sec.

Assuming that the drive is outfitted with spring assembly, the drive is opened for

2,8 sec. The drive should then still be within the spring assembly. This position is

allocated and stored as 0%.

With the same procedure the position for 100% is allocated and stored.

Simultaneously the motor running time is determined and saved as parameter tt.

Afterwards the controller sets the drive in the position before calibration.

Was the controller in automatic mode before calibration it will be set to automatic

mode again otherwise it remains in manual mode.

The following errors can be occure during calibration:

w the change of the Yp input is to small, no monitoring is possible

w the motion is in wrong direction

w the Yp input is broken

In these cases the automatic calibration will be stopped and the controller remains

in manual mode.

g

If the automatic calibration leads to no resonable results the calibration of the Yp

input can be done manual.

g

If the conroller reaches the positions of 0% or 100% the outputs will be switched

off. Also in manual mode it is not possible to exceed these limits.

g

Because no controller with continuouse output and Yp input is defined there

won't be the DAC function for this controlling type.

Special functions

DAC

®

– motor actuator monitoring

64

KS 90-1 / KS 92-1