Configuration 38, Out.5, Out.6 – West Control Solutions Pro-4 User Manual

Page 38: Logi, Configuration level

Advertising
background image

Configuration level

Configuration parameters

38

KS 90-1 / KS 92-1

Name Value range Description

Default

fOut

Forcing OUT3 (only visible with BlueControl!)

0

0

No forcing

1

Forcing via serial interface

Out.5

/

Out.6

Configuration parameters Out.2 = Out.1 except for: Default Y.1 = 0 Y.2 = 0

g

Method of operation and usage of output Out.1 to Out.6:

Is more than one signal chosen active as source, those signals are OR-linked.

LOGI

Name Value range Description

Default

L_r

Local / Remote switching (Remote: adjusting of all values by

front keys is blocked)

0

0

no function (switch-over via interface is possible)

1

always active

2

DI1 switches

3

DI2 switches (basic instrument or OPTION)

4

DI3 switches (only visible with OPTION)

5

è - key switches

SP.2

Switching to second setpoint SP.2

0

0

no function (switch-over via interface is possible)

2

DI1 switches

3

DI2 switches (only visible with OPTION)

4

DI3 switches (only visible with OPTION)

5

è - key switches

SP.E

Switching to external setpoint SP.E

0

0

no function (switch-over via interface is possible)

1

always active

2

DI1 switches

3

DI2 switches (only visible with OPTION)

4

DI3 switches (only visible with OPTION)

5

è - key switches

Y2

Y/Y2 switching

0

0

no function (switch-over via interface is possible)

2

DI1 switches

3

DI2 switches (only visible with OPTION)

4

DI3 switches (only visible with OPTION)

5

è - key switches

6

Ò - key switches