4.3 Set-point processing

The set-point processing structure is shown in the following picture:

4.3.1 Set-point gradient / ramp

To prevent setpoint step changes, a maximum rate of change is adjustable for

parameter r setpoint r r.SP. This gradient acts both in positive and negative

direction.

With parameter r.SP set to OFFas in the factory setting, the gradient is

switched off and setpoint changes are made directly.

Configuration level

KS 90-1 / KS 92-1

43

Set-point processing

0

Ü

Xeff

SP.2

SP.E
0/4...20 mA

Internal

set-point

*

Ö

SP.Hi

SP.Lo

r.SP

- LED

External

set-point

INP2

Limitation

Ramp

2. set-point

Effektive

set-point

Ü

+

8

The ramp starts at process value

with the following switchings:

- int / ext-setpoint switching

-

/

switching

- Manual-/ Automatic switching

- at power on

SP SP.2