Configuration 36, Out.1, Out.3 – West Control Solutions Pro-4 User Manual

Page 36: Out4, Configuration level

Advertising
background image

Configuration level

Configuration parameters

36

KS 90-1 / KS 92-1

Out.1

and Out.2

Name Value range Description

Default

O.Act

Method of operation of output OUT1

0

0

direct / normally open

1

inverse / normally closed

Y.1

Y.2

Controller output Y1/Y2

1

0

not active

1

active

Lim.1

Lim.2

Lim.3

Limit 1/2/3 signal

0

0

not active

1

active

dAc.A

Valve monitoring (DAC)

0

0

not active

1

active

LP.AL

Interruption alarm signal (LOOP)

0

0

not active

1

active

HC.AL

Heat current alarm signal

0

0

not active

1

active

HC.SC

Solid state relay (SSR) short circuit signal

0

0

not active

1

active

FAi.1

FAi.2

FAi.3

INP1/ INP2 / INP3 error signal

0

0

not active

1

active

dP.Er

PROFIBUS error

0

0

not active

1

active: Profibus trouble, no communication with this

instrument.

fOut

Forcing OUT1 (only visible with BlueControl!)

0

0

No forcing

1

Forcing via serial interface

Configuration parameters Out.2 = Out.1 except for: Default Y.1 = 0 Y.2 = 1

Out.3

and

Out4

Name Value range Description

Default

O.tYP

Signal type selection OUT3

0

0

relay / logic (only visible with current/logic voltage)

1

0 ... 20 mA continuous (only visible with current/logic/voltage)

2

4 ... 20 mA continuous (only visible with current/logic/voltage)

3

0...10 V continuous (only visible with current/logic/voltage)

4

2...10 V continuous (only visible with current/logic/voltage)

5

transmitter supply (only visible without OPTION)