Configuration level

KS 90-1 / KS 92-1

37

Configuration parameters

Name Value range Description

Default

O.Act

Method of operation of output OUT3 (only visible when O.TYP=0)

1

0

direct / normally open

1

inverse / normally closed

Out.0

-1999...9999

Scaling of the analog output for 0% (0/4mA or 0/2V, only visible

when O.TYP=1..5)

0

Out.1

-1999...9999

Scaling of the analog output for 100% (20mA or 10V, only visible

when O.TYP=1..5)

100

O.Src

Signal source of the analog output OUT3 (only visible when

O.TYP=1..5)

1

0

not used

1

controller output y1 (continuous)

2

controller output y2 (continuous)

3

process value

4

effective set-point Weff

5

control deviation xw (process value - set-point)

6

measured value position feedback Yp

7

measured value INP1

8

measured value INP2

9

measured value INP3

O.FAI

Failbehaviour, behaviour of the analog output, if the signal source

(O.Src) is disturbed.

0

0

upscale

1

downscale

Y.1

Y.2

Controller output Y1/Y2 (only visible when O.TYP=0)

0

0

not active

1

active

Lim.1

Lim.2

Lim.3

Limit 1/2/3 signal (only visible when O.TYP=0)

1

0

not active

1

active

dAc.A

Valve monitoring (DAC) (only visible when O.TYP=0)

0

0

not active

1

active

LP.AL

Interruption alarm signal (LOOP) (only visible when O.TYP=0)

(Loop-Alarm)

0

0

not active

1

active

HC.AL

Heating current alarm signal (only visible when O.TYP=0)

0

0

not active

1

active

HC.SC

Solidstaterelay(SSR)shortcircuitsignal(onlyvisiblewhenO.TYP=0)

0

0

not active

1

active

FAi.1

FAi.2

FAi.3

INP1/ INP2 / INP3 error (only visible when O.TYP=0)

1

0

not active

1

active

dP.Er

PROFIBUS error

0

0

not active

1

active: Profibus trouble, no communication with this instrument.