3.5.8 Self-tuning start

Start condition:

w For process evaluation, a stable condition is required. Therefore, the

controller waits until the process has reached a stable condition after

self-tuning start.

The rest condition is considered being reached, when the process value

oscillation is smaller than ± 0,5% of (rnG.H - rnG.L).

w For self-tuning start after start-up, a 10% difference from (SP.LO ... SP.Hi)

is required.

g

Self-tuning start can be blocked via BlueControl

®

(engineering tool) ( P.Loc).

Strt = 0

Only manual start by pressing keys Ù and È

simultaneously or via interface is possible.

Strt = 1

Manual start by press keys Ù and È simultaneously

via interface and automatic start after power-on and detection

of process oscillations.

3.5.9 Self-tuning cancellation

By the operator:

Self-tuning can always be cancelled by the operator. For this, press Ù and È

key simultaneously.With controller switch-over to manual mode after self-tuning

start, self-tuning is cancelled. When self-tuning is cancelled, the controller will

continue operating using the old parameter values.

By the controller:

If the Err LED starts blinking whilst self-tuning is running, successful self-tuning

is prevented due to the control conditions. In this case, self-tuning was cancelled

by the controller. The controller continues operating with the old parameters in

automatic mode. In manual mode it continues with the old controller output va-

lue.

Operation

KS 90-1 / KS 92-1

21

Self-tuning

Ada LED status

Signification

blinks

Waiting, until process

calms down

lit

Self-tuning is running

off

Self-tuning not activ

or ended