6 calibration level 61, Point correction 61, Calibration level (cal) 61 - 63 – West Control Solutions Pro-4 User Manual
Page 61: Offset correction 61, Rм щ, R ù r, Rr ù r, Rr ù, Rr щ м и
Advertising
Offset correction ( ConF/ InP.1 / Corr =1 ):
InL.1: The input value of the scaling point is displayed.
The operator must wait, until the process is at rest.
Subsequently, the operator acknowledges the input value by pressing
key Ù.
OuL.1: The display value of the scaling point is displayed.
Before calibration, OuL.1 is equal to InL.1.
The operator can correct the display value by pressing keys ÈÌ .
Subsequently, he confirms the display value by pressing key Ù.
Calibration level
KS 90-1 / KS 92-1
61
r
М
Щ
3 sec.
r
PArA
CAL
r Ù r
InP.1
Ù
r
InL.1
r
r Ù
r
:
OuL.1
r
r Ù
End
r
r Щ
М
И
1200
1199
°C
°F
SP.2
SP.E
para
func
Ada
Err