7.6 KS90-1 as Modbus master

a

This function is only selectable with BlueControl (engineering tool)!

The KS90-1 can be used as Modbus master ( ConF / othr / MASt = 1 ). The

Modbus master sends ist data to all slaves (Broadcast message, controller adress

0). It transmits its data (modbus adress AdrU) cyclic with the cycle time Cycl to

the bus. The slave controller receives the data transmitted by the masters and al-

locates it to the modbus target adress AdrO. If more than one data should be

transmitted by the master controller ( Numb > 1) , the modbus adress AdrU in-

dicates the start adress of the data that should be transmitted and AdrO indicates

the first target adress where the received data should be stored. The following

data will be stored at the logically following modbus target adresses.

With this it is possible e.g. to specify the process value of the master controller as

set-point for the slave controllers.

7.7 Back-up controller (PROFIBUS)

Back-up operation: calculation of the control outputs is in the master. The con-

troller is used for process value measurement, correcting variable output and for

display.

With master or communication failure, control is taken over independently and

bumplessly by the controller.

Special functions

KS 90-1 / KS 92-1

69

KS90-1 as Modbus master

Additions othr

(only visible with BlueControl!)

Name

Value range Description

Default

MASt

Controller is used as Modbus master

0

0

Slave

1

Master

Cycl

0...200

Cycle time [ms] for the Modbus master to transmit its data

to the bus.

60

AdrO

1...65535

Target address to which the with

AdrU

specified data is

given out on the bus.

1

AdrU

1...65535

Modbus address of the data that Modbus master gives to

the bus.

1

Numb

0...100

Number of data that should be transmitted by the Modbus

master.

0